Slaves are defined to the system when the module initializes the Master
command list. Each slave defined will be set to a state of one in this initial step. If
the Master port fails to communicate with a slave device (retry count expired on a
command), the Master will set the state of the slave to a value of 2 in the status
table. This suspends communication with the slave device for a user specified
scan count (ErrorDelayCntr value in the DFCM.config.PortX object for each port).
Each time a command in the list is scanned that has the address of a suspended
slave, the delay counter value will be decremented. When the value reaches
zero, the slave state will be set to one. This will enable polling of the slave.
In order to read the slave status table, ladder logic must be written. The ladder
logic must send a special block to the module to request the data. Each port has
a specific set of blocks to request the data as follows:
Block ID
Description
3002
Request for first 128 slave status values for Port 1
3003
Request for last 128 slave status values for Port 1
3102
Request for first 128 slave status values for Port 2
3103
Request for last 128 slave status values for Port 2
The format of these blocks is as shown below:
Offset
Description
Length
0
3002 to 3003 or 3102 to 3103
1
1 to 247
Spare
246
The module will recognize the request by receiving the special write block code
and respond with a read block with the following format:
Offset
Description
Length
0
Reserved
1
1
Write Block ID
1
2 to 129
Slave Poll Status Data
128
130 to 248
Spare
119
249
3002 to 3003 or 3102 to 3103
1
Ladder logic can be written to override the value in the slave status table to
disable slaves (state value of 3) by sending a special block of data from the
processor to the slave. Port 1 slaves are disabled using block 3000, and Port 2
slaves are disabled using block 3100. Each block contains the slave node
addresses to disable. The structure of the block is displayed below:
Offset
Description
Length
0
3000 or 3100
1
1
Number of Slaves in Block
1
2 to 201
Slave indexes
200
202 to 247
Spare
46
The module will respond with a block with the same identification code received
and indicate the number of slaves acted on with the block. The format of this
response block is displayed below: