Reference
MVI56-LTQ ♦ ControlLogix Platform
User Manual
Limitorque Valve Actuator Master Communication Module
Page 78 of 98
ProSoft Technology, Inc.
August 30, 2010
Member
Name
MX-DDC
UEC-3-DDC
DOut
Digital Output
Bit 00
01
02
03
04
05
06
07
08
09
10 to 15
Close Contactor
Open Contactor
AS-1
AS-2
AS-3
AS-4
AR-1, Opt
AR-2, Opt
AR-3, Opt
Network Relay
Not Used
Close Contactor
Open Contactor
User (K3)
SW-93 LED
SW-93 LED
User (K6)
N/A
N/A
Bits 08 - 15
Field Unit Software
Version ID
Din1
Digital Inputs 1
Bit 00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Remote Mode Selected
Thermal Overload Fault
Open Torque Switch
Open Limit Switch
Close Torque Switch
Close Limit Switch
Not Used
Not Used
User 0, Terminal-21
User 1, Terminal-10
User 2, Terminal-9
User 3, Terminal-6
User 4, Terminal-7
User 5, Terminal-5
User 6, Opt, Terminal-23
User 7, Opt, Terminal-24
Remote Mode Selected
Thermal Overload Fault
Open Torque Switch
Open Limit Switch
Close Torque Switch
Close Limit Switch
Aux. Open Input
Aux. Close Input
User 0, TB2-1
User 1, TB2-2
User 2, TB2-3
User 3, TB2-4
User 4, TB2-5
User 5, TB2-6
User 6, I/O Module Only
User 7, I/O Module Only
DIn2
Digital Inputs 2
Bit 00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Not Used
Not Used
Analog In 1 Lost
Analog In 2 Lost
Network A/B Lost
Not Used
DDC Bd. Present
I/O Opt Board Present
Not Used
Not Used
Not Used
Not Used
Phase Lost
Phase Reverse
User 8, Opt, Terminal-25
Not Used
Analog In 1 Lost
Analog In 2 Lost
Analog In 3 Lost
Analog In 4 Lost
Network A/B Lost
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Phase Lost
Phase Reverse
User 8, I/O Module Only
User 9, I/O Module Only
ComStatus
Communication
Status Code
See Trouble Shooting Section.
Do not use this word to determine Slave communication
status. Word N[ ]:1 (Status) bits 10 and 11 are preferred.
This is a module diagnostic word only.
ComCntr
Communication
Counter
This is a rollover counter (0 to 32767) which increments
upon completion of every successful communication
transaction with a slave. This counter will increment on
poll (read) commands as well as write commands.