Reference

MVI56-LTQ ♦ ControlLogix Platform

User Manual

Limitorque Valve Actuator Master Communication Module

Page 72 of 98

ProSoft Technology, Inc.

August 30, 2010

5.3.5 RS-485 Application Port(s)

The RS-485 interface requires a single two or three wire cable. The Common
connection is optional, depending on the RS-485 network devices used. The
cable required for this interface is shown below:

Note: Terminating resistors are generally not required on the RS-485 network, unless you are

experiencing communication problems that can be attributed to signal echoes or reflections. In

these cases, installing a 120-ohm terminating resistor between pins 1 and 8 on the module

connector end of the RS-485 line may improve communication quality.

If communication in the RS-422 or RS-485 mode does not work at first, despite
all attempts, try switching termination polarities. Some manufacturers interpret +
and -, or A and B, polarities differently.

RS-485 and RS-422 Tip

5.3.6 DB9 to RJ45 Adaptor (Cable 14)