Normal data transfer – ProSoft Technology MVI56-LTQ User Manual

Page 61

background image

MVI56-LTQ ♦ ControlLogix Platform

Reference

Limitorque Valve Actuator Master Communication Module

User Manual

ProSoft Technology, Inc.

Page 61 of 98

August 30, 2010

Normal data transfer includes the paging of the valve data found in the module’s
internal database in registers 0 to 1499, the status data and the done bit data
from the module to the processor. These data are transferred through read (input
image) blocks 0 to 7. Data transferred from the processor to the module is
through blocks 0 and 1. The structure and function of each block is discussed in
the following topics.

Normal Data Transfer

Read Block
These blocks of data transfer information from the module to the ControlLogix
processor. The structure of the input image used to transfer this data is shown
below:

Word

Description

0

Reserved

1

BTW ID Requested (0 or 1)

2 to 201

Valve Data (20 valves each block)

202 to 211

Done Bit Data

212 to 213

Product Code

214 to 215

Revision

216 to 217

Operating System

218 to 219

Run Number

220

Pass Count

221

Queue Size

222

BTR Count

223

BTW Count

224

BT Parse Count

225

BT Event Count

226

BT Error Count

227

Current Slave

228

Current Port

229

Alt Port

230

Special Poll Request

231

State

232

Comm State

233

CfgErr

234 to 248

Spare

249

BTR ID (0 to 7)

The Read Block ID is an index value used to determine the location of where the
data will be placed in the ControlLogix processor controller tag array of module
read data. Each transfer can move up to 200 words (block offsets 2 to 201) of
data representing the data for up to 20 valves. In addition to moving valve data,
the block also contains status data for the module. This last set of data is
transferred with each new block of data and is used for high-speed data
movement.