MVI56-LTQ Status Data Definition
This section contains a description of the members present in the LTQStat
object. This data is transferred from the module to the processor as part of each
read block.
Offset
Content
Description
212 to 213
Product
These two registers contain the product code of "LTQ5"
214 to 215
Revision
These two registers contain the product version for the current
running software.
216 to 217
OpSys
These two registers contain the month and year values for the
program operating system.
218 to 219
Run
These two registers contain the run number value for the
currently running software.
220
PassCnt
This value is incremented each time a complete program
cycle occurs in the module.
221
Queue
Number of messages present in the command queue waiting
for execution.
222
BTR_Cnt
This field contains the total number of read blocks transferred
from the module to the processor.
223
BTW_Cnt
This field contains the total number of write blocks transferred
from the processor to the module.
224
BlkParse
This field contains the total number of blocks successfully
parsed that were received from the processor.
225
BlkEvent
This field contains the total number of command event blocks
received from the processor. Each command received by the
module will cause this value to increment.
226
BlkErr
This field contains the total number of block errors recognized
by the module.
227
CurSlave
This field contains the index of the current slave being polled
by the module.
228
CurPort
This field contains the index of the current port on the module
being utilized. A value of 0 indicates the first port (Port A). A
value of 1 indicates the second port (Port B) is utilized.
229
AltPort
This field is set to 1 when the alternate port (not the primary
port) is being used due to a communication error.
230
SpecPoll
This field contains the value of 0, 1 or 2. A value of 0 indicates
a normal poll or command is being executed. A value of 1
indicates a special poll for TP_BEFORE_MID_T_HIGH
(register 55) is being executed. A value of 2 indicates a
special poll for registers 6 and 7 is being executed. A value of
3 to 65535 indicates the corresponding register is being
polled.
231
State
This field contains the module state machine value.
232
ComState
This field contains the module communication state machine
value.
233
CfgErr
This field contains the configuration error status for the
module. If an error in the module’s configuration is recognized,
this field will be set to a value other than zero.