Diagnostics and Troubleshooting

MVI56-LTQ ♦ ControlLogix Platform

User Manual

Limitorque Valve Actuator Master Communication Module

Page 38 of 98

ProSoft Technology, Inc.

August 30, 2010

4.1

LED Status Indicators

The LEDs indicate the module’s operating status as follows:

LED

Color

Status

Indication

CFG

Green

On

Data is being transferred between the module and a remote
terminal using the Configuration/Debug port.

Off

No data is being transferred on the Configuration/Debug port.

P1

Green

On

Data is being transferred between the module and the
Limitorque network on Port A.

Off

No data is being transferred on the port.

P2

Green

On

Data is being transferred between the module and the
Limitorque network on Port B.

Off

No data is being transferred on the port.

APP

Amber

Off

The MVI56-LTQ is working normally.

On

The MVI56-LTQ module program has recognized a
communication error on one of its ports.

BP ACT

Amber

On

The LED is on when the module is performing a write
operation on the backplane.

Off

The LED is off when the module is performing a read
operation on the backplane. Under normal operation, the LED
should blink rapidly on and off.

OK

Red/
Green

Off

The card is not receiving any power and is not securely
plugged into the rack.

Green

The module is operating normally.

Red

The program has detected an error or is being configured. If
the LED remains red for over 10 seconds, the program has
probably halted. Remove the card from the rack and re-insert
the card to restart the module’s program.

BAT

Red

Off

The battery voltage is OK and functioning.

On

The battery voltage is low or battery is not present. Allow
battery to charge by keeping module plugged into rack for 24
hours. If BAT LED still does not go off, contact ProSoft
Technology, as this is not a user serviceable item.