Configuration object (ltqcfg) – ProSoft Technology MVI56-LTQ User Manual
Page 22

Configuring the MVI56-LTQ Module
MVI56-LTQ ♦ ControlLogix Platform
User Manual
Limitorque Valve Actuator Master Communication Module
Page 22 of 98
ProSoft Technology, Inc.
August 30, 2010
2.2
Configuration Object (LTQCfg)
The configuration object LTQCfg contains all the configuration information
required by the module. Fill in the members of this object to set the parameters
required for each application. This data set will be transferred from the processor
to the module each time a restart (warm or cold boot) operation is requested.
Configuration of the module is performed by filling in the values in the module
object defined in the Controller Tags Edit Tags dialog box. Each parameter
required by the module has a defined location in the object. The following table
describes the structure of the object.
Name
Data Type
Description
BaudRate
INT
Baudrate for port (110 to 115.2K)
MsgRespTm
INT
Message Response Timeout
MaxSlaves
INT
Maximum number of slaves to consider
BTRMax
INT
Maximum BTR block count
BlkDelay
INT
Block transfer delay counter
LastState
INT
State for slave data on comm failure
NetPoll
INT
Network polling scheme (0=A/B, 1=A, 2=B)
PropDelay
INT
Propagation delay for messages
RTSOn
INT
RTS to TxD delay (milliseconds)
SpecPolling
INT
Special polling used (0=No, 1=T-MID, 2=Reg 6/7;
other numbers of the range 1 to 65535 refer to the
corresponding register).
Use_CTS
INT
Monitor CTS line (0=No, 1=Yes)
BlkFailCnt
INT
Number of failed transfers before COM shutdown
ActiveSlaves
INT[10]
Array to set active slaves (1-bit/slave)
Each parameter contained in this object is described in MVI56-LTQ Configuration
Data Definition (page 23). Ensure that you fill in each parameter carefully for
successful application of the module in a system.