beautypg.com

8technical data – ProSoft Technology ILX69-PBS User Manual

Page 89

background image

ILX69-PBS ♦ CompactLogix or MicroLogix Platform

Contents

PROFIBUS Slave Communication Module

User Manual

ProSoft Technology, Inc.

Page 89 of 102

March 20, 2015

8

Technical Data

In This Chapter

Technical Data - ILX69-PBS ..................................................................89

Technical Data - PROFIBUS .................................................................92

8.1

Technical Data - ILX69-PBS

Note: All technical data can be altered without notice.

ILX69-PBS

Parameter

Value

General

Description

PROFIBUS DP slave module

Function

PROFIBUS slave slot extension module for Rockwell
CompactLogix™ 1769 system which allows the PLC to
control exchange data on a PROFIBUS network.

Communication
Controller

Type

netX 100 processor

Integrated Memory

RAM

8 MB SDRAM

FLASH

16 MB serial Flash EPROM

Memory card

SD and SDHC card. Both types are supported if the card
features a SPI interface. The FAT12/16/32 formats are
supported. The exFAT format is not supported.
Capacity: Max. 4 GByte
Refer to section Removable Memory Card

SD Card Connector

e.g. FPS009-2405-0 push/push

Host Interface

1769 Backplane

Rockwell backplane interface:
Rockwell Mercury chip for 1769 backplane

PROFIBUS
Communication

Supported communication
protocol

PROFIBUS DP slave

PROFIBUS Interface

Transmission rate

9.6 kBit/s, 19.2 kBit/s, 31.25 kBit/s, 45.45 kBit/s,
93.75 kBit/s, 187.5 kBit/s, 500 kBit/s, 1.5 MBit/s,
3 MBit/s, 6 MBit/s, 12 MBit/s

Interface Type

RS-485, according EN 50170, refer to section PROFIBUS
Interface

Galvanic Isolation

Isolated

Isolation Voltage

500 VDC (from backplane)