beautypg.com

ProSoft Technology ILX69-PBS User Manual

Page 55

background image

ILX69-PBS ♦ CompactLogix or MicroLogix Platform

Contents

PROFIBUS Slave Communication Module

User Manual

ProSoft Technology, Inc.

Page 55 of 102

March 20, 2015

Slave Status

A 128 byte Slave Status field is transferred to the user program via the input data area
image. It contains the ILX69-PBS status, beginning with byte 8 of the input region. The
status information encompasses 32 bytes of static information and 96 bytes bytes reserved
for the extended status field. The content of the extended status is controlled by the
command "ExtStaSelect" byte in the Device Command Register in the user program (byte
offset 8 to 9).

Byte
Offset

Structure
member

Data
type

Description

Valid Values

8 to 9

ExtStaSelect

INT

Shows the extended status
information that is currently
transmitted in the field
"Extended Status Information"

0 = No extended status information
1 = Firmware version
2 = Slave configuration
3 = Master configuration
4 = Parameter data
6 = Reserved

10 to 11

ExtStaLen

INT

Number of valid bytes in the
region "Extended Status
Information"

Depends on the selected extended status
0 = 0 Byte
1 = 32 Byte
2 = 49 Byte
3 = 49 Byte
4 = 33 Byte
6 = 80 Byte

12 to 13

Baudrate

INT

Baud Rate on PROFIBUS
network

12000 = 12 MBaud
6000 = 6 MBaud
3000 = 3 MBaud
1500 = 1.5 MBaud
500 = 500 kBaud
187 = 187.5 kBaud
93 = 93.75 kBaud
9 = 9.6 kBaud
0 = Not detected

14

Busaddress

SINT

Bus Address of the slave

0 to 125

15

UserFlags

SINT

User Flags

D0 = Parameter data changed
D1 = Configuration data changed
D2 to D7 = Not Applicable

16 to 17

Ident

INT

Slave identification number

0EE1h

18 to 19

Reserved

INT

Reserved

Set to 0

20 to 21

InputDataLen

INT

Length of input data(*)

0 to 244

22 to 23

OutputDataLen

INT

Length of output data(*)

0 to 244

24 to 25

Reserved

INT

Reserved

Set to 0

26

Reserved

SINT

Reserved

Set to 0

27

Pad

SINT

Reserved

Set to 0

28 to 29

Watchdog
Time

INT

Current watchdog time

5 to 65535 ms

30 to 31

IrqCounter

INT

Indication of bus activity

0 to 0xFFFF

32 to 37

Dpv1StatReg

INT

DPV1 Status Register

See following section

38 to 39

Reserved

SINT

Reserved

Reserved

40 to 135 ExtStatusInfo

SINT[96]

Extended Status Information

See following section