ProSoft Technology ILX69-PBS User Manual
Page 59

ILX69-PBS ♦ CompactLogix or MicroLogix Platform
Contents
PROFIBUS Slave Communication Module
User Manual
ProSoft Technology, Inc.
Page 59 of 102
March 20, 2015
Structure member
Data type
Description
AlaAckResp
DINT
Alarm Acknowledge Responses
AlaAckErr
DINT
Alarm Acknowledge Errors
ErrRespUsr
DINT
Erroneous Responses from User
UnxRespUsr
DINT
Unexpected Responses from User
ILX69-PBS Input Data (PROFIBUS Network Output Data)
Starting at byte 136, the remainder of the ILX69-PBS input array is used for the PROFIBUS
network output data sent from the master to the ILX69-PBS. The data is then transferred
from the ILX69-PBS to the controller via the AOI. The maximum size of PROFIBUS network
output data is 244 bytes.
6.2.3 Output Array
Device Command Register
The Device Command Register is transferred from the controller to the ILX69-PBS via the
output data image. This register lies in the first 4 bytes of the output image.
Device Command Register
Byte Offset
Structure Member Data type
Description
0
MCB
SINT
Module Command Bits, see table below
1
Reserved
SINT
Reserved
2
Reserved
SINT
Reserved
3
ExtStaSelect
SINT
Extended Status Information Select, see table below
MCB - Module Command Bits
Bit Offset
Structure Member Data type
Description
0
Reserved
BOOL
Reserved
1
Reserved
BOOL
Reserved
2
Reserved
BOOL
Reserved
3
Reserved
BOOL
Reserved
4
Reserved
BOOL
Reserved
5
NRDY
BOOL
Not ready - With this bit, the user program can make
a controlled start or stop of the ILX69-PBS
communications with the PROFIBUS master.
6
INIT
BOOL
Initialization - With this bit, the user program can
execute a Reset (Warmboot) of the ILX69-PBS.
7
RST
BOOL
Reset - With this bit, the user program can execute a
Reset (Coldboot) of the ILX69-PBS.
Important: Using the RST Reset command will cause an immediate
interruption in bus communication. The connection to the network master