ILX69-PBS ♦ CompactLogix or MicroLogix Platform

User Manual

PROFIBUS Slave Communication Module

Page 24 of 102

ProSoft Technology, Inc.

March 20, 2015

4.2

ILX69-PBS Hardware Installation

This section describes how to install/uninstall the ILX69-

PBS into a CompactLogix™ system.

4.2.1 Safety Precautions

Obey the following property damage messages when installing, uninstalling or replacing the
ILX69-PBS.

Electrostatically sensitive devices

To prevent damage to the PLC and the ILX69-PBS, make sure that the ILX69-PBS is
grounded via the backplane of the PLC. Also make sure that you are discharged when
you install/uninstall the ILX69-PBS.

Device Destruction

Shut off the power supply of the PLC before you install the ILX69-PBS. Then install or
remove the ILX69-PBS to/from the PLC..

Use only the permissible supply voltage to operate the ILX69-PBS.

All I/O signal pins at the ILX69-PBS tolerate only the specified signaling voltage.

4.2.2 Installing the ILX69-PBS Module

A detailed description the installation of communication modules in
CompactLogix™ systems can be found in the installation manual for the
1769 CompactLogix™ controller from Rockwell Automation.


1
Install the ILX69-

PBS into a free slot in the CompactLogix™ controller. Make sure it is

within 2 slots of a power supply.

2 Check that the bus lever of the ILX69-PBS is in the unlocked (fully right) position.
3 Assemble the ILX69-

PBS and the CompactLogix™ module together by using the upper

and lower tongue-and-groove slots.

4 Move the ILX69-PBS back along the tongue-and-groove slots until the bus connectors

line up with each other.

5 Move the ILX69-PBS bus lever fully to the left until it clicks. Ensure it is locked firmly in

place.

6 Attach and lock an end cap terminator to the ILX69-PBS by using the tongue-and-groove

slots as before.

7

Apply power to the Rockwell CompactLogix™ controller.