MSB - Module Status Bits
Bit
Offset
Structure
Member
Data
Type
Description
0
Reserved
BOOL
Reserved, set to 0
1
Reserved
BOOL
Reserved, set to 0
2
Reserved
BOOL
Reserved, set to 0
3
Reserved
BOOL
Reserved, set to 0
4
Reserved
BOOL
Reserved, set to 0
5
COM
BOOL
Communication - When this bit is set, the communication
has started and the module is engaged in cyclic data
exchange with the master.
0 = Not communicating, 1 = Communicating
6
RUN
BOOL
Run - When this bit is set, the module is ready for
communication. Otherwise, an initialization error or
incorrect parameterization has occurred.
0 = Not running, 1 = Running
7
RDY
BOOL
Ready - When this bit is set, the module is operational. The
RDY bit should always be set by the module. If this bit is
not set, a system error has occurred and the
communication between controller and module is not
active.
0 = Not ready, 1 = Ready
Firmware Revision
This data field contains the current Firmware Revision of the ILX69-PBS. The Minor revision
is the low byte and the Major revision is the high byte. The mapping is shown below.
Byte
Offset
Structure
Member
Data
Type
Description
4
FwMinor
SINT
Firmware Minor Revision
5
FwMajor
SINT
Firmware Major Revision
6 to 7
Reserved
-
Reserved
Example:
If FwMajor = 10 and FwMinor = 1 then the firmware revision is 10.1.
Due to a different internal firmware numbering scheme than Major/Minor version, the
following method is used to utilize this information to support requirements for a major
revision/minor revision of the CompactLogix controller. Because the first release of the
ILX69-PBS internal firmware will start with at least V01.000, the first firmware version in
Major Minor scheme will be at least 10.00. Details are provided in the table below.
FW Revision
FW Major
FW Minor
V01.000
10
00
V01.001
10
01
…