ILX69-PBS ♦ CompactLogix or MicroLogix Platform

Contents

PROFIBUS Slave Communication Module

User Manual

ProSoft Technology, Inc.

Page 67 of 102

March 20, 2015

DPV1 Error Codes

Below are the PROFIBUS DPV1 error codes.


Error Code 1

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Error Code (see below)

Error Class (see below)

Error Class

Description

Error Code

0 to 9

Reserved

10

Application

0 = Read Error
1 = Write Error
2 = Module Failure
3 to 7 = Reserved
8 = Version Conflict
9 = Feature not Supported
10 to 15 = User Specific

11

Access

0 = Invalid Index
1 = Write Length Error
2 = Invalid Slot
3 = Type Conflict
4 = Invalid Area
5 = State Conflict
6 = Access Denied
7 = Invalid Range
8 = Invalid Parameter
9 = Invalid Type
10 to 15 = User Specific

12

Resource

0 = Read Constrain Conflict
1 = Write Constrain Conflict
2 = Resource Busy
3 = Resource Unavailable
4 to 7 = Reserved
8 to 15 = User Specific

13 to15

User Specific


Error Code 2