DPV1 Alarm

The DPV1 Class 1 Alarm Request is used to indicate a DPV1 Alarm to the master. The
MSG instruction Request/Response format is as follows.


ILX69PBS.CONTROL.DPV1.Alarm.Request

Parameter

Data Type Value

Description

.Status

DINT

0x0000

Status of Alarm Request message

.Command

DINT

0x0221C

Command code

.SlaveAddress SINT

Slave address

.AlarmType

SINT

Type of received alarm specified

.SlotNumber

SINT

0 to 255

Slot number module causing alarm

.Specifier

SINT

Alarm specifier

.Function

SINT

.Reserved

SINT

0

Reserved


ILX69PBS.CONTROL.DPV1.Alarm.Response

Parameter

Data Type Value

Description

.Status

DINT

0x0000

Status of Alarm Request message, 0 = OK

.Command

DINT

0x0221C

Command code

.SlaveAddress SINT

Slave address

.AlarmType

SINT

Type of received alarm specified

.SlotNumber

SINT

0 to 255

Slot number module causing alarm

.Specifier

SINT

Alarm specifier

.Function

SINT

.ErrorDecode

SINT

Error code

.ErrorCode1

SINT

Detailed error code

.ErrorCode2

SINT

User-specific error code