ProSoft Technology ILX69-PBS User Manual
Page 47

ILX69-PBS ♦ CompactLogix or MicroLogix Platform
Contents
PROFIBUS Slave Communication Module
User Manual
ProSoft Technology, Inc.
Page 47 of 102
March 20, 2015
Word
Offset
Configuration
word
Data
type
Low/High
Byte
Description
Valid values
37
Local:1:C.Data[37]
SINT
LOW Byte
Net Mask
00.00.00.00 through
FF.FF.FF.FF
…
…
HIGH Byte
39
Local:1:C.Data[39]
SINT
LOW Byte
Gateway Address
00.00.00.00 through
FF.FF.FF.FF
…
…
HIGH Byte
41
Local:1:C.Data[41]
-
-
Reserved
Set to 0
5.2.4 Configuration Parameters
Bus Address
The ILX69-PBS has two rotating address switches to set the network address from 0 to 99.
If you need to assign the ILX69-PBS to an address above 99, set both address switches to
0. The module will take the address parameter from the configuration data array.
Address
Switches
Configuration
Address Parameter
Active
Bus Address
Description
1 to 99
N/A
1 to 99
Address switches are valid
0
0 to 125
0 to 125
Configuration parameter is valid
0
> 125
N/A
Invalid (will cause an initialization error)
Force User Configuration
If this value is set to 1, the ILX69-PBS will not start network communication until the master
and slave configurations match.
If this value is set to 0, the slave accepts the configuration sent from the master.