ProSoft Technology ILX69-PBS User Manual

Page 34

background image

Contents

ILX69-PBS ♦ CompactLogix or MicroLogix Platform

User Manual

PROFIBUS Slave Communication Module

Page 34 of 102

ProSoft Technology, Inc.

March 20, 2015

5 Click on the A

DVANCED

tab (Offline). This option assigns the S

TATION

A

DDRESS

(PROFIBUS Slave ID) of the ILX69-PBS.

It also determines how the ILX69-PBS obtains its configuration by C

ONFIGURATION

T

YPE

.

In most applications, O

BTAIN FROM

M

ASTER

is sufficient. With this option, the

configuration is done within the PROFIBUS master software and sent to the ILX69-PBS.

The O

BTAIN FROM

L

ADDER

option is a unique option that allows the CompactLogix

controller to "lock" the ILX69-PBS PROFIBUS configuration. Once this option is
selected, you will manually configure the PROFIBUS I/O data in the Module
Configuration

section of the tab. The PROFIBUS Master’s configuration for this slave

must match 100%, or communications will fail.

6 Click OK.
7 The ILX69-PBS module is now visible in the I/O Configuration tree.