User Manual
PROFIBUS Slave Communication Module
Page 34 of 102
ProSoft Technology, Inc.
March 20, 2015
5 Click on the A
DVANCED
tab (Offline). This option assigns the S
TATION
A
DDRESS
(PROFIBUS Slave ID) of the ILX69-PBS.
It also determines how the ILX69-PBS obtains its configuration by C
ONFIGURATION
T
YPE
.
In most applications, O
BTAIN FROM
M
ASTER
is sufficient. With this option, the
configuration is done within the PROFIBUS master software and sent to the ILX69-PBS.
The O
BTAIN FROM
L
ADDER
option is a unique option that allows the CompactLogix
controller to "lock" the ILX69-PBS PROFIBUS configuration. Once this option is
selected, you will manually configure the PROFIBUS I/O data in the Module
Configuration
section of the tab. The PROFIBUS Master’s configuration for this slave
must match 100%, or communications will fail.
6 Click OK.
7 The ILX69-PBS module is now visible in the I/O Configuration tree.