6.3.2 Standard Messaging

This section contains the description of the Standard Message supported by the ILX69-PBS.

DPS Diagnostic Request

The Diagnostic Request command can be used by the controller user application to
generate a single diagnostic request to a master. The MSG instruction
Request/Confirmation format is as follows.


FSPMS Set Slave Diag Request

Offset Variable

Type

Description

0

ulSta

UINT32

Status = 0 (S_OK)

4

ulCmd

UINT32

Request = 0x040E

8

fExtDiagOverflow

UINT8

Set the bit to indicate that more diagnostic data are
available as diagnostic data can be transferred with
abExtDiagData[ ]

9

fExtDiagFlag

UINT8

If set, diagnostic is sent as extended diagnostic.

10

bRes[2]

UINT8

Reserved padding bytes, set to 0

11

bRes[2]

UINT8

Reserved padding bytes, set to 0

12

abExtDiagData[ ]

UINT8[237]

Diagnostic data block to be transferred


FSPMS Set Slave Diag Confirmation

Offset Variable

Type

Description

0

ulSta

UINT32

Status
0 = Set Slave Diag successful
0 != Set Slave Diag failed

4

ulCmd

UINT32

Request = 0x040F


Status Code Name

Description

0xC0000009

TLR_E_INVALID_PARAMETE
R

The parameter of the “SetSlaveDiag” request is invalid.
Check if the length and consistency of the
ExtDiagData[] are correct.