Contents

ILX69-PBS ♦ CompactLogix or MicroLogix Platform

User Manual

PROFIBUS Slave Communication Module

Page 62 of 102

ProSoft Technology, Inc.

March 20, 2015

The content of abExtDiagData[ ] follows the PROFIBUS decoding of extended diagnostic
data. The abExtDiagData[ ] can contain one or more diagnostic blocks. If the content does
not follow these rules, the confirmation will be returned with an error. Following table
describes the PROFIBUS-specified extended diagnostic blocks.

Extended Diag
Block

Byte 0 Byte 1

Byte 2

Byte 3

Byte 4 to n

Note

Alarm Block

Header

Alarm Type Slot Number Alarm Specifier DiagUserData[59

]

2*

Status Block

Header

Status
Type

Slot Number Status

Specifier

DiagUserData[59
]

1*

Device-related Block

Header

User data

User data

User data

User data

2*

Module-related Block

Header

Module0...7 Module8...15 Module16...23 Module24...255

1*

Channel-related Block Header

Channel

Error

-

-

1*

Note: The FSPMS_SetSlaveDiag service only sends the Status, Module and Channel-related Blocks.

The Alarm and the Device-related diagnostic blocks are listed here only to give an overview of PROFIBUS-
defined Extended Diagnostic Blocks. These blocks cannot be sent with the service “FSPMS_SetSlaveDiag”. The

Alarm Block will be transferred separately with the service “FSPMS_C1_Alarm_Notification”. The Device-related

Block is reserved for DPV0 Slaves only.

Example:

The following example shows how to transmit an extended diagnostic with two blocks; one
channel-related and one status block. The c

hannel diagnostic reports an “Overload”. The

status block reports a user-

specific status with the string “HELP” in Slot1.