5 wiring the fault alarm contact – PLANET IGS-10020HPT User Manual
Page 43

User’s Manual
2.
Tighten the wire-clamp screws for preventing the wires from loosening.
1 2
3 4 5
6
DC
1 DC
2
Figure 2-18
6-Pin Terminal Block Power Wiring Input
Model Name
Positive (+) Pin
Negative (-) Pin
Input Voltage
IGS-10020MT
Pin 2 / 6
Pin 1 / 5
DC 12~48V, AC 24V
IGS-10020PT/HPT
Pin 1 / 5
Pin 2 / 6
DC 48V
IGS-10020HPT
Pin 1 / 5
Pin 2 / 6
DC 48V
IGS-10080MFT
Pin 1 / 5
Pin 2 / 6
DC 12~48V, AC 24V
IGS-12040MT
Pin 1 / 5
Pin 2 / 6
DC 12~72V, AC 24V
1. The wire gauge for the terminal block should be in the range of 12 ~ 24 AWG.
2. When performing any of the procedures like inserting the wires or tightening the wire-clamp screws,
make sure the power is OFF to prevent from getting an electric shock.
2.1.5 Wiring the Fault Alarm Contact
The fault alarm contacts are in the middle (3 & 4) of the terminal block connector as the picture shows below. Inserting the wires,
the Industrial Managed Switch will detect the fault status of the power failure, or port link failure (available for managed model).
The following illustration shows an application example for wiring the fault alarm contacts
Insert the wires into the fault alarm contacts
43