5 wiring the faulty alarm contact – PLANET MGSD-10080F User Manual
Page 40
User’s Manual of MGSD-10080F
40
2.
Tighten the wire-clamp screws for preventing the wires from losing.
1
2
3
4
5
6
DC 1
DC 2
+
-
+
-
Figure 2-4 6-Pin Terminal Block Power Wiring Input
1. The wire gauge for the terminal block should be in the range of 12 ~ 24 AWG.
2. When performing any of the procedures like inserting the wires or tighten the wire-clamp screws,
make sure the power is OFF to prevent from getting an electric shock.
2.1.5 Wiring the Faulty Alarm Contact
The fault alarm contacts are in the middle (3 & 4) of the terminal block connector as the picture shows below. Inserting the wires,
the Managed Switch will detect the fault status of the power failure, or port link failure (available for managed model). The
following illustration shows an application example for wiring the fault alarm contacts
Insert the wires into the faulty alarm contacts
1. The wire gauge for the terminal block should be in the range of 12 ~ 24 AWG.
2. When performing any of the procedures like inserting the wires or tighten the wire-clamp screws, make
sure the power is OFF to prevent from getting an electric shock.