Reset diag, Reset meter to factory defaults – Precision Digital PD6000 User Manual
Page 84

Model PD6000 Analog Input Process Meter Instruction Manual
84
Reset Meter to Factory Defaults
When the parameters have been changed in a way that is difficult to
determine what’s happening, it might be better to start the setup
process from the factory defaults.
Instructions to load factory defaults:
1. Enter
the
Advanced
Features menu. See Advanced Features
Menu, page 66.
2. Press Up arrow to go to Diagnostics menu
3. Press and hold Right arrow for five seconds, press
Enter when display flashes reset.
Note: If Enter is not pressed within three seconds, the display re-
turns to the Diagnostics menu.
4. The meter goes through an initialization sequence (similar as on
power-up), and loads the factory default settings.
996000
G P d
Run Mode
20.000
mA
reset
diaG
Press & hold Menu for
3 sec to access
Advanced features
Press & hold right
arrow for
3 sec to reset meter
Note: The dual-scale selection for level applications (LEVEL) is not re-
set to the single scale factory default. This can be changed using
the Setup – Input menu.