beautypg.com

Modbus rtu serial communications, Relay connections, Relay4 relay3 – Precision Digital PD6000 User Manual

Page 20: Relay2 relay1, Voltage signal, Input signal, Input signal 3-wire voltage transducer, Figure 10. relay connections

background image

Model PD6000 Analog Input Process Meter Instruction Manual

20

-

+

+

Voltage

Signal

mA+

P-

2

1

3

5

4

P+

V+

COM

INPUT SIGNAL

mA+

P-

2

1

3

5

4

P+

V+

COM

INPUT SIGNAL

3-Wire Voltage

Transducer

Signal

-

Figure 9. Voltage Input Connections

The meter is capable of accepting any voltage from -10 VDC to +10 VDC.

Modbus RTU Serial Communications

Serial communications connection is made to an RJ45 connector la-
beled M-LINK on Figure 5. Use the PDA1232 for RS-232 interfacing or
the PDA1485 for RS-422/485 interfacing. The same port is used for
interfacing with all expansion modules (e.g. external relays, digital I/O).
Use the PDA1200 meter copy cable for meter-to-meter interfacing for
cloning purposes (i.e. copying settings from one meter to other meters).

Relay Connections

Relay connections are made to two six-terminal connectors labeled
RELAY1 – RELAY4 on Figure 5. Each relay’s C terminal is common
only to the normally open (NO) and normally closed (NC) contacts of the
corresponding relay. The relays’ C terminals should not be confused
with the COM (common) terminal of the INPUT SIGNAL connector.

C

NO

NO

NC

NC

C

RELAY4

RELAY3

4

3

6

5

2

1

C

NO

NO

NC

NC

C

RELAY2

RELAY1

4

3

6

5

2

1

Figure 10. Relay Connections

This manual is related to the following products: