Model PD6000 Analog Input Process Meter Instruction Manual

11

AUTO
INITIALIZATION

When power is applied to the meter, relays will reflect the
state of the input to the meter.

Isolated 4-20 mA Transmitter Output

OUTPUT
SOURCE

Process variable (PV), max, min, set points 1-8, Modbus
input, or manual control mode

SCALING RANGE 1.000 to 23.000 mA for any display range

CALIBRATION

Factory calibrated: 4.000 to 20.000 = 4-20 mA output

ANALOG OUT
PROGRAMMING

23.000 mA maximum for all parameters:
Overrange, underrange, max, min, and break

ACCURACY

± 0.1% of span ± 0.004 mA

TEMPERATURE
DRIFT

0.4 µA/

C max from 0 to 65C ambient,

0.8 µA/

C max from -40 to 0C ambient

Note: Analog output drift is separate from input drift.

ISOLATED
TRANSMITTER
POWER SUPPLY

Terminals I+ & R: 24 VDC

 5% @ 40 mA maximum; may

be used to power the 4-20 mA output or other devices.
Refer to Figure 5 on page 18 and Figure 13 on page 22.

EXTERNAL LOOP
POWER SUPPLY

35 VDC maximum

OUTPUT LOOP
RESISTANCE

Power supply

Minimum

Maximum

24 VDC

10

 700

35 VDC (external)

100

 1200

Modbus

®

RTU Serial Communications

SLAVE ID

1 – 247 (Meter address)

BAUD RATE

300 – 19,200 bps

TRANSMIT
TIME DELAY

Programmable between 0 and 199 ms
or transmitter always on for RS-422 communication

DATA

8 bit (1 start bit, 1 or 2 stop bits)

PARITY

Even, Odd, or None with 1 or 2 stop bits

BYTE-TO-BYTE
TIMEOUT

0.01 – 2.54 second

TURN AROUND
DELAY

Less than 2 ms (fixed)

Note: Refer to the PD6000/PD7000 Modbus Register Tables located at
www.predig.com for details.