Setting the relay operation ( relay ) – Precision Digital PD6000 User Manual
Page 43
Model PD6000 Analog Input Process Meter Instruction Manual
43
Setting the Relay Operation (relay)
This menu is used to set up the operation of the relays.
CAUTION! During setup, the relays do not follow the input and they will
remain in the state found prior to entering the Relay menu.
1. Relay
action
a. Automatic reset only (non-latching)
b. Automatic + manual reset at any time (non-latching)
c.
Latching (manual reset only)
d. Latching with Clear (manual reset only after alarm condi-
tion has cleared)
e. Pump alternation control (automatic reset only)
f.
Sampling (the relay is activated for a user-specified time)
g. Off (relay state controlled by Interlock feature)
2. Set
point
3. Reset
point
4. Fail-safe
operation
a. On
(enabled)
b. Off
(disabled)
5. Time
delay
a. On delay (0-999.9 seconds)
b. Off delay (0-999.9 seconds)
6. Relay action for loss (break) of 4-20 mA input (ignore, on, off)