Precision Digital PD6000 User Manual
Page 28
Model PD6000 Analog Input Process Meter Instruction Manual
28
Display Parameter
Action/Setting
Description
d-Inty
Display
intensity
Set display intensity level from 1 to 8
RELaY
Relay
Enter the Relay menu
RLY 1
Relay 1
Relay 1 setup
Act 1
Action 1
Set relay 1 action
Auto
Automatic
Set relay for automatic reset
A-man
Auto-manual
Set relay for automatic & manual reset any
time
LatCH
Latching
Set relay for latching operation
Lt-CLr
Latching-
cleared
Set relay for latching operation with ma-
nual reset only after alarm condition has
cleared
Altern
Alternate
Set relay for pump alternation control
Sampl
Sampling
Set relay for sampling operation
OFF
Off
Disable relay and front panel status LED
(Select Off to enable Interlock feature)
Set 1
Set 1
Program set point 1
RSt 1
Reset 1
Program reset point 1
RLY 2
Relay 2
Relays 2-8 setup
Note: Relays 5-8 are shown, only if ex-
pansion relay module is installed.
FaiLSF
Fail-safe
Enter Fail-safe menu
FLS 1
Fail-safe 1
Set relay 1 fail-safe operation
on
On
Enable fail-safe operation
FLS 2
Fail-safe 2
Set relays 2-8 fail-safe operation
DeLAY
Delay
Enter relay Time Delay menu
DLY 1
Delay 1
Enter relay 1 time delay setup
On 1
On 1
Set relay 1 On time delay
OFF 1
Off 1
Set relay 1 Off time delay
DLY 2
Delay 2
Enter relays 2-8 time delay setup
break
Loop break
Set relay condition if loop break detected