Specifications, General – Precision Digital PD6000 User Manual
Page 8

Model PD6000 Analog Input Process Meter Instruction Manual
8
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C.
General
DISPLAY
Main display: 0.60" (15 mm) high, red LEDs 
Second display: 0.46" (12 mm) high, red LEDs 
6 digits each (-99999 to 999999), with lead zero blanking 
DISPLAY 
INTENSITY 
Eight user selectable intensity levels
DISPLAY 
UPDATE RATE 
5/second (200 ms)
OVERRANGE
Display flashes
999999
UNDERRANGE
Display flashes
-99999
DISPLAY 
ASSIGNMENT 
The main (Big) and small (Little) displays may be assigned 
to PV1, PV2, PCT, max/min, alternate max & min, set 
points, units (small display only), and Modbus input. 
PROGRAMMING 
METHODS 
Four front panel buttons, digital inputs, PC and MeterView Pro 
software, Modbus registers, or cloning using Copy function. 
NOISE FILTER
Programmable from 2 to 199 (0 will disable filter)
FILTER BYPASS Programmable from 0.1 to 99.9% of calibrated span
RECALIBRATION All ranges are calibrated at the factory. Recalibration is
recommended at least every 12 months.
MAX/MIN 
DISPLAY 
Max/min readings reached by the process are stored until 
reset by the user or until power to the meter is turned off. 
PASSWORD
Three programmable passwords restrict modification of 
programmed settings. 
Pass 1: Allows use of function keys and digital inputs 
Pass 2: Allows use of function keys, digital inputs and editing set/reset points 
Pass 3: Restricts all programming, function keys, and digital inputs. 
NON-VOLATILE 
MEMORY 
All programmed settings are stored in non-volatile memory 
for a minimum of ten years if power is lost. 
POWER 
OPTIONS 
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max 
or jumper selectable 12/24 VDC 
 10%, 15 W max
FUSE
Required external fuse: UL Recognized, 5 A max, slow 
blow; up to 6 meters may share one 5 A fuse 
ISOLATED 
TRANSMITTER 
POWER SUPPLY 
Terminals P+ & P-: 24 VDC
 5% @ 200 mA max (standard),
(12/24 VDC powered models rated @ 100 mA max). 
5 or 10 VDC @ 50 mA max, selectable with internal jumper J4.