Theoretical recommendations for installation

Technical dept. - All rights reserved by MCZ Group S.p.A. - Reproduction prohibited

2.6. FLUE PIPE CONNECTION

The inner dimensions of the flue pipe must not exceed 20 X 20 cm or a

diameter of 20 cm. If the dimensions are larger or the flue pipe is in

poor condition (e.g. cracks, poor insulation etc.) you are advised to

insert a stainless steel pipe of a suitable diameter into the flue pipe.

This steel pipe must extend along the entire length of the flue pipe until

it reaches the top.

Use suitable tools to check that there is a minimum draught of 10 Pa.

Install an inspection point on the base of the flue pipe for regular

checks and cleaning. Checks and cleaning must be performed

annually.

Make the connection to the flue pipe using connections and pipes

recommended by us.

You MUST check that a windproof chimney is installed in accordance

with standards in force.

This type of connection (even when there is a

temporary loss of current) ensures that smoke is

discharged.

2.7. CONNECTION TO AN EXTERNAL DUCT USING

AN INSULATED OR DOUBLE-WALL PIPE

The internal dimensions of the external duct must be between a

minimum of 10 X 10 cm or a diameter of 10 cm and a maximum of 20

X 20 or a diameter of 20 cm.

Use suitable tools to check that there is a draught of 10 Pa.

Use only smooth, stainless steel, insulated (double-wall) pipes inside

the stove (stainless steel hoses are not permitted). These pipes must

be fixed to the wall.

Install an inspection point on the base of the external vertical duct for

regular checks and cleaning. Checks and cleaning must be

performed annually.

Make the connection to the flue pipe using connections and pipes

recommended by us.

You MUST check that a windproof chimney is installed in accordance

with standards in force.

This type of connection (even when there is a

temporary loss of current) ensures that smoke is

discharged.

2.8. CONNECTION TO THE FLUE PIPE

For correct operation, the connection between the stove and the flue

pipe must be at least 3% of the stove in horizontal sections. The total

length of these sections must not exceed 2 - 3 metres. The vertical

section from one T-union to another (change of direction) must be at

least 1.5 metres.

Use suitable tools to check that there is a minimum draught of 10 Pa.

Install an inspection point on the base of the flue pipe for regular

checks and cleaning. Checks and cleaning must be performed

annually.

Make the connection to the flue pipe using connections and pipes

recommended by us.

You MUST check that a windproof chimney is installed in accordance

with standards in force.

This type of connection (even when there is a

temporary loss of current) ensures that smoke is

discharged.

1) Windproof chimney
2) Flue pipe
3) Inspection point

1) Windproof chimney
2) Flue pipe
3) Inspection point

1) Windproof chimney
2) Flue pipe
3) Inspection point

3-5 %

2 - 3 mt. MAX

0,5 mt.

H

>

1

,5

m

t.

3

2

1

0.5 mt.

1

2

3

1.5 mt

0.5 mt.

2

1

3