MCZ Philo User Manual
Page 14
PELLET STOVES
Chapter 2
USE AND MAINTENANCE MANUAL
page
14
Theoretical recommendations for installation
Technical dept. - All rights reserved by MCZ Group S.p.A. - Reproduction prohibited
2.6. FLUE PIPE CONNECTION
The inner dimensions of the flue pipe must not exceed 20 X 20 cm or a
diameter of 20 cm. If the dimensions are larger or the flue pipe is in
poor condition (e.g. cracks, poor insulation etc.) you are advised to
insert a stainless steel pipe of a suitable diameter into the flue pipe.
This steel pipe must extend along the entire length of the flue pipe until
it reaches the top.
Use suitable tools to check that there is a minimum draught of 10 Pa.
Install an inspection point on the base of the flue pipe for regular
checks and cleaning. Checks and cleaning must be performed
annually.
Make the connection to the flue pipe using connections and pipes
recommended by us.
You MUST check that a windproof chimney is installed in accordance
with standards in force.
This type of connection (even when there is a
temporary loss of current) ensures that smoke is
discharged.
2.7. CONNECTION TO AN EXTERNAL DUCT USING
AN INSULATED OR DOUBLE-WALL PIPE
The internal dimensions of the external duct must be between a
minimum of 10 X 10 cm or a diameter of 10 cm and a maximum of 20
X 20 or a diameter of 20 cm.
Use suitable tools to check that there is a draught of 10 Pa.
Use only smooth, stainless steel, insulated (double-wall) pipes inside
the stove (stainless steel hoses are not permitted). These pipes must
be fixed to the wall.
Install an inspection point on the base of the external vertical duct for
regular checks and cleaning. Checks and cleaning must be
performed annually.
Make the connection to the flue pipe using connections and pipes
recommended by us.
You MUST check that a windproof chimney is installed in accordance
with standards in force.
This type of connection (even when there is a
temporary loss of current) ensures that smoke is
discharged.
2.8. CONNECTION TO THE FLUE PIPE
For correct operation, the connection between the stove and the flue
pipe must be at least 3% of the stove in horizontal sections. The total
length of these sections must not exceed 2 - 3 metres. The vertical
section from one T-union to another (change of direction) must be at
least 1.5 metres.
Use suitable tools to check that there is a minimum draught of 10 Pa.
Install an inspection point on the base of the flue pipe for regular
checks and cleaning. Checks and cleaning must be performed
annually.
Make the connection to the flue pipe using connections and pipes
recommended by us.
You MUST check that a windproof chimney is installed in accordance
with standards in force.
This type of connection (even when there is a
temporary loss of current) ensures that smoke is
discharged.
1) Windproof chimney
2) Flue pipe
3) Inspection point
1) Windproof chimney
2) Flue pipe
3) Inspection point
1) Windproof chimney
2) Flue pipe
3) Inspection point
3-5 %
2 - 3 mt. MAX
0,5 mt.
H
>
1
,5
m
t.
3
2
1
0.5 mt.
1
2
3
1.5 mt
0.5 mt.
2
1
3