Error

Code

(Hex)

Description

Cause

Possible Solution

16

Object does not exist

An unsupported object was specified.

Correct the class or instance setting.

1F

Vendor-specific error

Attempted to change a drive constant that cannot be

changed while the drive is running.

Attempted to change a drive constant to a value outside

the setting range.

Stop the drive.

Specify a value within the setting range.

20

Invalid parameter

Attempted to change to a data value outside the setting

range.

Specify a data value within the setting range.

Note:

Refer to the MEMOBUS/Modbus Data Table in the MEMOBUS/Modbus Communications chapter of the drive manual for a list of monitor

data using the MEMOBUS/Modbus message area.

u

Option Error Codes

n

Option Fault Monitors U6-98 and U6-99

The option can declare error/warning conditions via drive monitor parameters on the drive digital operator as shown in

Table

17

.

Table 17 Option Fault Monitor Descriptions

Fault Condition

Fault Declared

Status Value

(U6-98/U6-99)

Description

No Fault

n/a

0

No faults

Force Fault

EF0

3

Network sent a message to force this node to the fault

state.

Network Link Down

BUS ERROR

1100

No network link to option.

Connection Timeout

BUS ERROR

1101

The node timer (Requested Packet Interval) timed out.

Duplicate IP Address

BUS ERROR

1102

This node and at least one other node have the same IP

Address.

Default MAC Address

None

1103

Factory default MAC Address programmed into the

option. Return for reprogramming.

Two drive monitor parameters, U6-98 and U6-99 assist the user in network troubleshooting.
• U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared upon drive power-up.
• U6-99 displays the present option status. U6-99 is cleared upon a network-issued fault reset and upon power-up.
If another fault occurs while the original fault is still active, parameter U6-98 retains the original fault value and U6-99 stores

the new fault status value.

13 Troubleshooting

62

YASKAWA SIEP YAICOM 15A V1000 Option Dual-Port EtherNet/IP SI-EN3D/V Technical Manual