Option fault code conversion table – Yaskawa V1000 Option Dual Port EtherNet/IP SI-EN3D/V Technical Manual User Manual
Page 45

Instance
ID
Attribute
Name
Description
Get
Set
Size
Range
Default
1
11
Warning
Warning
0: No Warning
1: Warning
O
–
Byte
–
0
1
12
Fault Reset
Fault Reset
0: No Fault Reset
1: Fault Reset
O
O
Byte
0, 1
0
1
13
Fault Code
Current Fault
details.
O
–
Word
–
0000
1
15
Control from
Net (Status)
Run Command from the option
0: The Run command is not from the
option
1: Enables the Run command from
option
O
–
Byte
–
0
1
16
NetFaultMode Normal 2 (Vendor Specific)
O
–
Byte
–
2
1
17
Force Fault
External Fault
0: No External Fault
1: External Fault (EF0)
Triggered by the rising edge of the
signal.
O
O
Byte
0, 1
0
1
18
Force Status
External Fault status
0: No External Fault
1: External Fault (EF0)
Triggered by the rising edge of the
signal.
O
–
Byte
–
0
n
Option Fault Code Conversion Table
Drive Fault Code (Hex)
(MEMOBUS/Modbus 0080 Hex)
Option Fault Code (Hex)
Description
2
3220
DC Bus Undervolt (Uv1)
3
5110
CTL PS Undervolt (Uv2)
4
3222
MC Answerback (Uv3)
5
2130
Short Circuit (SC)
6
2120
Ground Fault (GF)
7
2300
Over Current (oC)
8
3210
DC Bus Overvolt (ov)
9
4200
Heatsink Overtemp (oH)
10
4210
Heatsink Max Temp (oH1)
11
2220
Motor Overload (oL1)
12
2200
Drive Overload (oL2)
13
2221
Overtorque Det 1 (oL3)
14
2222
Overtorque Det 2 (oL4)
15
7110
DynBrk Transistor (rr)
16
7112
DynBrk Resistor (rH)
17
9000
External Fault 3 (EF3)
18
9000
External Fault 4 (EF4)
19
9000
External Fault 5 (EF5)
20
9000
External Fault 6 (EF6)
21
9000
External Fault 7 (EF7)
27
3130
Input Phase Loss (PF)
28
3130
Output Phase Loss (LF)
29
5210
Motor Overheat 1 (PTC Input) (oH3)
30
5300
Operator Disconnected (oPr)
31
6320
EEPROM R/W Error (Err)
32
3210
Motor OverHeat 2 (PTC Input) (oH4)
10 General Class Objects
YASKAWA SIEP YAICOM 15A V1000 Option Dual-Port EtherNet/IP SI-EN3D/V Technical Manual
45