beautypg.com

Flagged, Refer to high, For details – Yaskawa V1000 Option Dual Port EtherNet/IP SI-EN3D/V Technical Manual User Manual

Page 38

background image

u

High Speed/Torque Status Input (Vendor Specific Yaskawa Electric (YE) Assy) - 166
(0xA6)

If an error occurs while trying to read from the dynamic parameters, the appropriate error bit in Assembly 166 will be set. If

more information about the nature of the error is needed, the extended error status can be read explicitly through Class 4,

Instance 0xA6, Attribute 0x64. This will return 20 Bytes with each dynamic parameter in Assembly 166 having a Byte

dedicated to its extended error status.

Output Instance

Word

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

166

0

0

Faulted

Alarm

Ready

Speed

Agree

Fault Reset

REV

Running

ZSP

Running

1

Multi-

Function

Photo-

coupler 2

Multi-

Function

Photo-

coupler 1

Multi-

Function

Digital

Output

LOCAL/

REMOTE

Uv

oPE

1

2

Motor Speed (Low Byte)

3

Motor Speed (High Byte)

2

4

Torque Actual (Low Byte), not supported

5

Torque Actual (High Byte), not supported

3

6

PG Count Value (Low Byte)

7

PG Count Value (High Byte)

4

8

Frequency Command (Low Byte)

9

Frequency Command (High Byte)

5

10

Output Frequency (Low Byte)

11

Output Frequency (High Byte)

6

12

Output Current (Low Byte)

13

Output Current (High Byte)

7

14

Parameter F7-35

Default: Terminal A2 Input (Low Byte)

15

Parameter F7-35

Default: Terminal A2 Input (High Byte)

8

16

Main Circuit DC Voltage (Low Byte)

17

Main Circuit DC Voltage (High Byte)

9

18

Error Code (Low Byte)

19

Error Code (High Byte)

10

20

<1>

Parameter F7-33

Default: Alarm Code (Low Byte)

21

<1>

Parameter F7-33

Default: Alarm Code (High Byte)

9 Input Assemblies (Drive Produces)

38

YASKAWA SIEP YAICOM 15A V1000 Option Dual-Port EtherNet/IP SI-EN3D/V Technical Manual