5 installation procedure – Yaskawa V1000 Option Dual Port EtherNet/IP SI-EN3D/V Technical Manual User Manual
Page 18

Option ground terminal
Figure 17 Connect the Ground Wire to the Option
14.
Connect the Ethernet communication cable to the option modular connector (CN1) port 1.
To connect the option to a network, firmly connect RJ45 8-pin shielded twisted pair Cat5e cable(s) into the modular
connector ports (see
).
IGMP Snooping
Switches implementing IGMP Snooping are strongly recommended. When IGMP Snooping is used, devices will only
receive the multicast packets in which they are interested.
Communication Cable Specifications
Only use cable recommended for EtherNet/Industrial Protocol (EtherNet/IP™). Using a cable not specifically
recommended may cause the option or drive to malfunction. Refer to the ODVA website for more information on
network cabling (http://www.odva.org).
The dual RJ45 network ports on the option board act as a switch to allow for flexibility in cabling topology. For example,
a traditional star network topology may be employed by using a single port on the option board. Alternatively, a daisy-
chained approach may be employed by using both RJ45 ports. The daisy-chained approach reduces the requirements
of central switch ports. A ring topology is also possible.
Figure 18 Communication Cable Ports
STOP
(Hz)
(Hz)
(A)
(V)
V1000
STOP
(Hz)
(Hz)
(A)
(V)
V1000
STOP
(Hz)
(Hz)
(A)
(V)
V1000
STOP
(Hz)
(Hz)
(A)
(V)
V1000
STOP
(Hz)
(Hz)
(A)
(V)
V1000
STOP
(Hz)
(Hz)
(A)
(V)
V1000
STOP
(Hz)
(Hz)
(A)
(V)
V1000
STOP
(Hz)
(Hz)
(A)
(V)
V1000
STOP
(Hz)
(Hz)
(A)
(V)
V1000
Star Topology
Daisy-Chained Topology
Ring Topology
Figure 19 Topology Options
5 Installation Procedure
18
YASKAWA SIEP YAICOM 15A V1000 Option Dual-Port EtherNet/IP SI-EN3D/V Technical Manual