Speed and Torque Control Output - 22 (0x16)
Output Instance
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
22
0
0
–
–
–
–
–
Fault Reset
–
Run Fwd
1
–
1
2
Speed Reference (Low Byte)
3
Speed Reference (High Byte)
2
4
Torque Reference/Torque Limit (Low Byte)
5
Torque Reference/Torque Limit (High Byte)
Name
Description
Run Fwd
Forward Run Command
0: Stop
1: Forward Run
Fault Reset
Fault Reset
(0 to 1 transition: Fault Reset)
Speed Reference
Speed Command
Sets drive speed reference.
Speed reference data: Frequency reference/2
SS
(SS: Speed scale)
Setting range: 0 to 0xFFFF
Example: setting a reference of 4096 with a speed scale of 2:
Speed reference data = 4096/2
2
= 1024 = 0x0400 Hex
Unit depends on o1-03.
Torque Reference/Torque
Limit
Torque Reference/Torque Limit
Sets the Torque Reference/Torque Limit in units of 0.1%.
Sets the Torque Reference when using Torque Control (d5-01 = 1).
Sets the Torque Limit when using Speed Control (d5-01 = 0).
The Torque Reference and Torque Limit are disabled with F6-06 = 0.
u
Extended Speed and Torque Control Output - 23 (0x17)
Output Instance
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
23
0
0
–
NetRef
NetCtrl
–
–
Fault Reset
Run Rev
Run Fwd
1
–
1
2
Speed Reference (Low Byte)
3
Speed Reference (High Byte)
2
4
Torque Reference/Torque Limit (Low Byte)
5
Torque Reference/Torque Limit (High Byte)
Name
Description
Run Fwd
Forward Run Command
0: Stop
1: Forward Run
Run Rev
Reverse Run Command
0: Stop
1: Reverse Run
Fault Reset
Fault Reset
(0 to 1 transition: Fault Reset)
NetCtrl
Run command from Network
0: Depends on b1-02
1: Enables the run command from network
NetRef
Speed reference from Network
0: Depends on b1-01
1: Enables the speed reference from network
Speed Reference
Speed Command
Sets drive speed reference.
Speed reference data: Frequency reference/2
SS
(SS: Speed scale)
Setting range: 0 to 0xFFFF
Example: setting a reference of 4096 with a speed scale of 2:
Speed reference data = 4096/2
2
= 1024 = 0x0400 Hex
Unit depends on o1-03.
8 Output Assemblies (Drive Consumes)
22