Yaskawa SI-EN3D User Manual
Page 19

<3> Enabled in CLV, AOLV/PM, and CLV/PM control modes (A1-02 = 3, 6, or 7). When enabled, d5-01 determines whether the value is read as the
Torque Limit value (d5-01 = 0) or read as the Torque Reference value (d5-01 = 1). In CLV/PM, this value is read as the Torque Limit.
<4> The setting specifies that the Torque Reference or Torque Limit is to be provided via network communications (F6-06 = 1). The motor may rotate
if no torque reference or Torque Limit is supplied from the PLC.
<5> Parameter setting value is not reset to the default value when the drive is initialized.
<6> Cycle power for setting changes to take effect.
<7> When F7-13 is set to 0, parameters F7-01 to F7-12 must be set, and all IP Addresses (as defined with parameters F7-01 to F7-04) must be unique.
<8> When F7-14 is set to 0 or 2, parameter F7-15 must be set.
<9> Setting range differs depending on drive software version. PRG: 1020 and earlier, Range: 0 to 2
PRG: 1021 and later, Range: 0 to 8
<10> Setting range differs depending on drive software version. PRG: 1020 and earlier, Range: 10, 100
PRG: 1021 and later, Range: 10; 100 to 102
Table 6 Option Monitors
No.
Name
Description
Value Range
U6-80 to
U6-83
Online IP Address
IP Address currently available; U6-80 is the most significant octet
0 to 255
U6-84 to
U6-87
Online Subnet
Subnet currently available; U6-84 is the most significant octet
0 to 255
U6-88 to
U6-91
Online Gateway
Gateway currently available; U6-88 is the most significant octet
0 to 255
U6-92
Online Speed
Link Speed
10: 10 Mbps
100: 100 Mbps
U6-93
Online Duplex
Duplex Setting
0: Half, 1: Full
U6-94
Port 2 Duplex
Port 2 Duplex Setting
0: Half, 1: Full
U6-95
Port 2 Speed
Port 2 Link Speed
10: 10 Mbps
100: 100 Mbps
U6-98
First Fault
First Option Fault
–
U6-99
Current Fault
Current Option Fault
–
6 Related Drive Parameters
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
19