Option led display, Power-up diagnostics – Yaskawa SI-EN3D User Manual
Page 10

u
Option LED Display
The option has four LEDs.
Bi-color Status LEDs:
• Module status (MS) red/green
• Network status (NS) red/green
Ethernet LEDs:
• Network speed - 10/100 (MS) green
• Link status and network activity - LINK/ACT (NS) red/green
The operational states of the option LEDs after completion of the power-up diagnostic LED sequence are described in
Table 3 Option LED States
Name
Display
Operating Status
Remarks
Color
Status
MS
–
OFF
Power supply OFF
Power is not being supplied to the drive.
Green
ON
Normal operation
The option is operating normally and initialization is
complete.
Green
Flashing
Standby/Initializing
The option is in process of configuring or waiting for
configuration information.
Red
Flashing
Non-fatal error occurred
The option has detected a recoverable minor fault such
as incomplete configuration.
Red
ON
Fatal error occurred
The option has detected an unrecoverable major fault.
Green/Red
Flashing
Option self-test
The option is in self-test mode.
NS
–
OFF
Power supply OFF
–
Green
ON
Online communications
established
The option is online and has established connections.
Green
Flashing
Not connected
The option is online without an established connection.
Red
Flashing
Minor fault
A minor recoverable fault has occurred.
Red
ON
Major fault
The option detected a duplicate IP address.
Green/Red
Flashing
Option self-test
The option is in self-test mode.
10/100
<1>
Green
OFF
10 Mbps is established
–
Green
ON
100 Mbps is established
LINK/ACT
<1>
Green
OFF
LINK is not established
Green
ON
LINK is established
Green
Flashing
LINK is established and there is
network activity.
<1> Remove the cover to check the status of the LED. Be careful not to touch the main circuit terminals or the control board in the drive.
n
Power-Up Diagnostics
An LED test is performed each time the drive is powered up. The initial boot sequence may take several seconds. After the
LEDs have completed the diagnostic LED sequence, the option is successfully initialized. The LEDs then assume operational
.
Table 4 Power-Up Diagnostic LED Sequence
Sequence
Module Status (MS)
Network Status (NS)
Time (ms)
1
Green
OFF
250
2
Red
OFF
250
3
Green
OFF
–
4
Green
Green
250
5
Green
Red
250
6
Green
OFF
–
4 Option Components
10