5.2 Trip Settings
Figure 5.1 Overvoltage and undervoltage disconnect
Table 5.3 Standards for voltage trip levels and trip times
Table 5.4 Default frequency trip levels and trip times
5.3 Compliance
Nom. grid
Vmin2
[V]
T_Vmin2
[s]
Vmin1
[V]
T_Vmin1
[s]
Vmax1
[V]
T_Vmax1
[s]
Vmax2
[V]
T_Vmax2
[s]
Nominal voltage
400 V
Standard
200.00
0.16
352.00
2.00
440.00
1.00
480.00
0.16
Range
160 to
240
0.1 to 3.0 300 to
380
0.5 to 3.0 420 -
480
0.5 to 3.0
440 -
520
0.1 to 3.0
Nominal voltage:
480 V
Standard
240.00
0.16
423.00
2.00
528.00
1.00
576.00
0.16
Range
192 to
288
0.1 to 3.0 360 - 456 0.5 to 3.0 504 -
576
0.5 to 3.0
528 -
624
0.1 to 3.0
Fmin2
[Hz]
T_Fmin2
[s]
Fmin1
[Hz]
T_Fmin1
[s]
Fmax1
[Hz]
T_Fmax1
[s]
Fmax2
[Hz]
T_Fmax2
[s]
Standard
57.00
0.16
59.30
10.00
60.50
0.16
-
-
Range
56.5 to
57.5
0.1 to 3.0 57.0 to
59.8
0.16 to
300
60.1 to
60.9
0.16 to
3.0
60.1 to
61.0
0.1 to 3.0
INFORMATION
The values apply only to IEEE 1547.
International standards
STP 60 series
Efficiency
EU efficiency, Standard: EN 50530
CEC efficiency, Standard: CEC Directive
Test procedure: Performance Test Protocol for Evaluating Inverters Used in
Grid-Connected
Photovoltaic Systems (Draft): March 1, 2005
EC Low-Voltage Directive
2006/95/EC