PV-Related Events

Figure 4.2 PV-related events

System-Related Events

ID

Status
message

Description

Measure

DGO

Hotline PV

103

PV current is
too high/
waiting

Too many PV modules
connected in parallel. Should
only appear on newly installed
systems.

Check number of strings in
parallel and current ratings. Has
the current limit been exceeded?
Reconnect strings in parallel.

-

-

-

115,
260

PV ISO too
low

The resistance between the PV
strings and ground PE) is too
low for the inverter to be
commissioned. This will force
the inverter to make a new
measurement after ten minutes.

Make a visual inspection of all PV
cables and modules for correct
installation according to the
installation manual. The event
could indicate that the PE
connection is missing.

-

-

-

258

PV voltage
too high/
waiting

The DC voltage is too high.

Make sure that PV system and
layout correspond to
recommendations in the manuals.

-

-

-

278

DC voltage warning.

Make sure that PV system and
layout correspond to
recommendations in the manuals.

-

-

-

ID

Status
message

Description

Measure

DGO

Hotline PV

2000

Communication assembly is
booting.

-

-

-

-

2010,
2011

The software update of the
main CPU has been started/is
finished.

-

-

-

-

2012 to
2018

The software update failed.

Restart the software update. If an
error occurs during the update,
contact the Service.

-

-

-

2030

Transmitting grid code to CPU
failed.

If the occurs repeatedly, contact
the Service.

-

-

-

2050,
2051

Ethernet connection is active /
disconnected.

No measures required. This error
identifies bad Ethernet cables.

-

-

-

2052,
2053

Transmitting the grid code from
SMA Inverter Manager to
STP 60-10 has been started /
stopped.

-

-

-

-