beautypg.com

5 technical data, 1 specifications – SMA STP 60-US-10 Installation User Manual

Page 45

background image

SMA Solar Technology AG

5  Technical Data

Installation Guide

STP60-10-IA-xx-10

45

5 Technical Data

5.1 Specifications

Parameter

STP 60-10

AC
Nominal apparent power

1)

60 kVA

Nominal active power

2)

60 kW

Reactive power range

1)

0 to 60 kVAr

Nominal AC voltage (voltage range)

3P + PE (WYE) / 400-480 V (+/- 10 %)

Supported grounding systems

TT, TN

Nominal AC current

3 x 87 A

Max. AC current

3 x 87 A (3 x 72 A @ 480 V)

AC total harmonic distortion (THD at nominal output power)

< 1%

Inrush current

9.2 A/5 ms

Maximum residual output current

49.8 A RMS over three periods

Power factor – standard

> 0.99 at nominal power

Displacement power factor - regulated

0.8 overexcited to 0.8 underexcited

Stand-by power consumption (for communication)

3 W

Nominal power frequency (range)

50/60 Hz (+/- 10%)

DC
Input voltage range

565 to 1,000 V at 400 Vac

680 to 1000 V at 480 Vac

Nominal DC voltage

630 V at 400 Vac
710 V at 480 Vac

MPPT voltage range - nominal power

570 to 800 V at 400 Vac
685 to 800 V at 480 Vac

Max. DC voltage

1,000V

Min power on the grid

100 W

Max. DC MPPT current

4)

110 A

Max. DC short-circuit current

4)

150 A

MPP tracker/Input per MPPT

1/1 (when using an external PV array junction box)

Overvoltage categories

AC: Overvoltage category III (OVC III),

PV: Overvoltage category II (OVC II)

Efficiency
Max. efficiency EU/CEC

98.8%

EU efficiency at 630 V

DC

98.3%

CEC efficiency at 400/480 V

AC

98.0%/98.5%