beautypg.com

Lc connector, Precautions – H3C Technologies H3C SecPath L1000-A Load Balancer User Manual

Page 77

background image

69

Model

Central

wavele

ngth

Fiber

mode

Fiber

diameter

(μm)

Bandwidth

(MHz*km)

Max

transmission

distance

Specification (dBm)

Optical

transmit

power

Receivi

ng

sensitiv

ity

Optic

al

satur

ation

SFP-XG-L

X-SM131
0

1310
nm

SMF 9/125 N/A

10 km (6.21
miles)

–8.2 to +
0.5

≤–10.3 +0.5

SFP-XG-L
H40-SM

1550

1550
nm

SMF 9/125 N/A

40 km (24.86
miles)

–4.7 to +
4

≤–11.3 –1.0

LC connector

The L1000-A supports only the LC connector.

Figure 54 LC connector

(1) Dust plug

(2) LC connector

(3) Optical fiber

Precautions

Make sure the fiber connector and fiber type match the transceiver module type.

The optical interfaces on some cards have shielded covers. Remove the shielded covers before
using the optical interfaces. Optical interfaces must be installed with shielded covers when they

are not in use. Keep them safely.

Fiber connectors must be protected under safe and reliable outer packing, and be fitted with dust

caps. Fiber connectors must be installed with dust caps when they are not in use. Take care not to
scratch their end face. Replace the dust cap if it is loose or polluted.

Before connecting a fiber, use dust free paper and absolute alcohol to clean the end face of the
fiber connector. You can brush the end face only in one direction. You also need to brush the end

face of the fiber port.

Never bend or curve a fiber when connecting it. After a fiber is installed well, the bend radius must
be not less than 10 cm (3.94 in).

If the fiber has to pass through a metallic board hole, the hole must have a sleek and fully filleted
surface (the filleting radius must be not less than 2 mm, or 0.08 in). When passing through a