EH330, EH430 and ECC Condensing Unit

Remote Low Side Cuber Service Manual

July 2013

Page 45

Refrigerant Recovery

Recover the refrigerant from the ball valve access valves in this condensing unit.

1. Shut unit off. Confirm ball valves are in the open position.

2. To speed recovery use 3 Schrader valve removal / access port tools and remove the

valve cores from the ball valve access valves.

3. Attach refrigeration manifold to all three ports (use two manifolds or two extra hoses

and a tee).

If only two connections are available, connect to Liquid and Suction.

For single point recovery, connect to liquid ball valve.

4. Attach recovery system and recover refrigerant.

Liquid

Vapor

Suction

Core Removal & Access

Valve Example