beautypg.com

Place remote system – Scotsman EH330 C with ECC Condensing Unit ECC1200 User Manual

Page 13

background image

EH330, EH430 and ECC Condensing Unit

Remote Low Side Cuber Service Manual

July 2013

Page 12

Place Remote System

Roof preparation
Most installations of this system will place the

condensing unit on the roof of a building. The roof

must be physically able to accept the load of the

equipment and the roofing material must be prepared

to prevent water leaks.

Follow local codes for the placement and attachment

of the equipment.

Location
The condensing unit requires unobstructed air flow

to operate efficiently. A four foot space between

each intake side and a wall or other cabinet is

recommended.

Do not place where it will pick up hot discharged air

from an air conditioner or other refrigeration system

condensing unit.

Space must also be reserved for service on the

condensing unit.

Roof Piercing:
The roof (or wall) must have an opening

large enough for the three refrigeration tubes

and the control wire to pass through. The

minimum recommended size is 4” ID. In

most areas the power supply may also pass

through the same passage. If there isn’t a

passage one must be created. In most cases

this must be done by a licensed and bonded

roofer in order to maintain the roof’s integrity.

Roof Pipe Curb or Pitch Pocket:
To avoid potential kinking of the refrigeration tubing,

avoid small, tight radius types of covers on pitch

pockets.

Suggestions:
In most cases a mechanical lift, boom truck or crane

will be required to hoist the condensing unit.

Mount unit to roof rails or curbs and secure with lag

screws or similar field supplied fasteners.

Orient the assembled unit so that the unit’s mounts

are parallel to the pitch of the roof to allow water to

drain freely.

Do NOT place the unit directly onto roof rock.

This manual is related to the following products: