EH330, EH430 and ECC Condensing Unit

Remote Low Side Cuber Service Manual

July 2013

Page 42

Problem or Symptom

Possible Cause

Probable Correction

Low capacity

Dirty condenser

Clean condenser

Air temperature intake to condens-

er very high

Re-orient condenser to avoid hot

air intake

Water temperature intake to ice

making section very high

Check for hot water supply to ice

machine due to mal-functioning or

non-existent hot water check valve

at dishwashing sink

Ice broken up and stuck between

reservoir and curtain, happens

almost every cycle

Ice thickness set too thin
Ice very uneven, check superheat
Slow harvest, check headmaster

Storage bin or dispenser not hold-

ing ice properly

Check drains for water flow from

ice machine (separate to correct)

or restriction

High volume of drinks dispensed,

cold plate melting ice

Suggest pre-cooler for water sup-

ply to cold plate

Vapor inlet valve leaks through

slightly during the freeze cycle

Check valve body for similar

temperatures on inlet and outlet,

the outlet should be colder and

frost develops on the tubes to the

evaporators

Exceeding maximum freeze time,

compressor unit trips on high dis-

charge temp

Check condenser bypass valve

Poor ice formation - very cloudy

and misshapen

Dirty water system

Clean the water distributor to re-

move built up mineral scale

Low refrigerant charge.

Add several pounds of refrigerant

to check. If low on charge, locate

leak. Recover refrigerant, repair

leak, replace drier, evacuate to 300

microns and weigh in the name-

plate charge.

Whistling noise at condensing unit

during harvest

By pass and liquid inlet valve coils

not getting power

Check harness

Service Diagnosis