Scotsman EH330 C with ECC Condensing Unit ECC1200 User Manual

Page 31

background image

EH330, EH430 and ECC Condensing Unit

Remote Low Side Cuber Service Manual

July 2013

Page 30

Operational Characteristics 1800 lb system (ECC1800/EH430)

Cycle Times @ Condenser Temp/Cabinet Temp/Water Temp in degrees F.

70/70/50

90/90/70

120/110/100

Freeze

10 to 12 minutes

12 to 14 minutes

17 to 19 minutes

Harvest

1.5 to 2 minutes

1.5 minutes

1 minute

System Pressures @ Condenser Temp/Cabinet Temp/Water Temp in degrees F

70/70/50

90/90/70

120/110/100

Suction at head, end of Freeze 24 to 25 PSIG

29 to 32 PSIG

32 to 35 PSIG

Suction at head, Harvest - Peak 80 to 100 PSIG

90 to 110 PSIG

140 to 160 PSIG

Discharge at Condensing Unit:

Freeze - 5 minutes in

240 to 260 PSIG

250 to 270 PSIG

370 to 380 PSIG

Headmaster maintains a minimum discharge pressure during freeze of 217 PSIG + 25, -15 PSIG.

CPR Valve Setting: 55 - 60 PSIG.

Note: CPR allows a maximum low side pressure at the compressor. Maximum only occurs during harvest.

Refrigerant Charge
• 1800 - 232 oz
Compressor Amps, 1800
• Three Phase - 10 to 14
Batch Weight: 14 - 15 lb

Discharge Pressure Cut Out Switch
• Cuts Out at: 450 PSIG Resets at: 350 PSIG