The line set must be routed between the condensing unit and the ice maker’s location. During the transition

from quick connects to braze connections, the ice maker, condensing unit and line set may or may not have

quick connects, use this chart as a guideline for the proper action based on what is available at the site.

Condensing unit has sweat connections Condensing unit has quick connects

Ice making head has

sweat connections

If line set does not have quick connects,

route and use as is.

If line set has quick connects, recover

refrigerant from line set and cut all quick

connects off.

Compressor packs C1200CP,

C1410CP and C1800CP may be

connected to this head and will have

quick connects. If line set has quick

connects, recover refrigerant from line

set and cut one end of quick connects

off.

If line set does not have quick

connects, must use KTE6-EH stub kit

to add for condensing unit end.

Ice making head has

quick connects (prior

models of EH330 and

EH430)

If line set has quick connects, recover

refrigerant from line set and cut one end

of quick connects off.

If line set does not have quick connects,

must use KTE6-EH stub kit to add for ice

machine end.

If line set does not have quick

connects, must use KTE6-EH stub kit

to add for ice machine end.

Use the quick connects to make the

connection.

In all cases the line set will need to be shortened to fit.

Do NOT leave excess line set exposed outdoors,

especially on a roof.

Refrigerant Recovery and System Evacuation Notice
In the event the refrigerant must be recovered from this system and the system evacuated, recover and

evacuate from the three ball valve access valves.