Changing the battery
If the battery symbol shown below
displays 0%, the battery should be
changed within the next week.
100%
50%
0%
System bus
Heating system bus system
This controller can be expanded
modularly by connecting additional
modules to the integrated bus.
As supplied, the system can be
used to control the following
components of a heating system
1-8 Heating appliances (
modulating or switching)
1-15 Mixed weather-based
heating circuits
0-15 Room controller (digital
or analogue)
1
Solar energy system (2
collectors, 2 tanks)
1
Solid fuel boiler
Bus code
On mixer controllers and control
panels
The bus code (00-15; parameter
in the Specialist menu) is a means
of numbering the system's heating
circuits. Each control module and
each mixer module contains the
number of the associated heating
circuit, in the form of a bus code.
- Heating circuit numbers
(00-15) must not be assigned
twice.
- Heating circuit numbers 00 and
01 must not both be used
at the same time.
- The heating circuits are
numbered sequentially, starting
with “01”.
- Please only use heating
circuit number 00 for replacement
controllers, if “00” has been
used in the replaced controller.
Preassigned numbers
Heating circuit 1 01
After setting all bus codes,
the heating system must
be fully powered down once.
NOTE
The different components are
simply connected to the system
bus. The modules register with the
system automatically and search
for their communication partners
using the set bus code (heating
circuit number or boiler number).