General mode of operation

Heating circuit regulation

Weather-based regulation

The set heating curve is used to

determine the boiler or supply

temperature appropriate to the

measured outdoor temperature,

such that with a properly

configured heating system in the

reference room, approximately the

set room target temperature value

is achieved.

=> The precise setting of the

heating curve is extremely

important for weather-based

regulation.

The circulation pump is

regulated based on the weather.

The circulation pump is switched on

when there is demand for heating

and in frost protection mode.
Room sensor influence

The current room temperature can

be factored into the calculation of

the required supply temperature by

installing a room temperature sensor.

The influence factor (parameter

list) can be set between 0

(regulation purely based on

the weather) and 20 (room

temperature-based regulation

with only a slight influence from

the outdoor temperature). In the

position “----” room temperature-

based regulation is deactivated.

The positions “----” and “0” show

differences for demand-oriented

circulation pump switching.

Water heating

The hot water programme of

the control module affects Hot

water target temperature I of the

connected main controller. The

hot water programme of the main

controller is a separate programme.

frost protection temperature, the

room target temperature for the

corresponding heating circuit is

set to 5°C. The heating circuit is

enabled:

- Pumps are switched on

- Request for heat is sent

to the boiler

“----” => Outdoor frost protection

sensor is deactivated

The function is cancelled if the

outdoor temperature climbs

above the set frost protection

temperature by 1K.

Frost protection via the room

sensor

If the room temperature drops

below 5°C, the frost protection

function is activated.

The room target temperature for

the corresponding heating circuit

is set to 5°C. The heating circuit is

enabled:

- Pumps are switched on

- Request for heat is sent to the

boiler

Condition for shutdown:

Room temperature-based regulation

The room temperature exceeds

the set target value.

Weather-based regulation

The outdoor temperature exceeds

the target room temperature value

or the target supply temperature

value by 20°C.

If the room sensor influence is
“0”, after a one-off demand
for heating during the
reduction period, the pump
runs continuously.

NOTE

When the circulation pumps are

shut down, there is a lag period

of 5 minutes, if the burner was

switched on in the last 5 minutes

before the pump shutdown.

Pump lag

The controller effectively prevents

the pumps from seizing due to

extended shutdown periods.

The integrated protection function

switches on all pumps, which have

not been run in the past 24 hours,

daily at 12:00pm for 5 seconds.

Pump seizing protection

Frost protection function

The frost protection mechanism

prevents the heating system from

freezing by automatically switching

on heating mode.

Outdoor frost protection sensor

If the measured outdoor

temperature drops below the set

Every 10 minutes, an automatic

check is performed to determine

that the settings values of the

controller are within the specified

limits. If a value is found to be

outside of the limits, then it is

replaced by the associated default

value. Error 81 appears in the

Favourites line on the standard

display to indicate that a value

exceeded the permissible range.

In this case, the user should check

the key settings of the controller.

The warning symbol goes out after

the unit is restarted (RESET).

EEPROM check

If the mixer has not moved for

24 hours, is is fully opened once

at approx. 3:00am. During this

time, the heating circuit pump is

switched off. The maximum supply

temperature is monitored. The

process is cancelled if maximum

supply temperature – 5K.

Mixer seizing protection

Heating demand-dependent

switching

Demand-dependent circulation

pump switching shuts down the

circulation pumps if there is no

demand for heating. At the same

time, the mixers are closed.

Circulation pump switching