Heating circuit 2 (continued) – REMKO MHP-Manager Wireless Remote Control User Manual
Page 13

Parameter
Value
range
Default
OV
Comments
Heating curve
0.00 - 3.00 1.20
The curve's slope indicates by how many degrees the supply
temperature will change if the outdoor temperature rises or falls by 1 K.
Information on adjustment:
With cold outdoor temperatures and a low room temperature =>
increase heating curve (and vice-versa)
With high outdoor temperatures (e.g. 16°C) and a low room
temperature => correction using the target room temperature
Heating curve diagram (adjustment aid)
Supply temperature [°C]
0,2
0,4
0,6
0,8
1
1,2
1,5
2
2,5
3
20
40
60
80
100
20 16 12 8 4 0 -4 -8 -12 -16
Outdoor temperature [°C]
Setting 0 => Purely room-based regulation
The heating curve is best adjusted when the outdoor
temperature is below 5°C. Changing the heating curve setting must
be carried out in small steps and in larger time intervals (at least 5
to 6 hours), because the system must first adjust to the new values
after every change in the heating curve.
Reference values:
- Floor heating
S = 0.4 to 0.6
- Radiator heating
S = 1.0 to 1.5
Heating curve
adaptation
OFF/ON
OFF
Only active when the analogue room device FBR (room sensor +
mode selection) and an outdoor sensor are connected.
Function to automatically set the heating curve
Start-up requirements:
- Outdoor temperature < 8°C
- Operating mode Automatic (I or II)
- Duration of the reduction phase at least 6 hours
The current room temperature is measured at the beginning of the
reduction period. This temperature is used over the following 4 hours
as the target value for room-based regulation. The heating curve
is calculated from the values captured by the controller in this time
period for the target supply temperature and outdoor temperature.
If adaptation is interrupted, e.g. by a start-up unloading device or
the hot water demand of an external heating circuit, the warning
triangle appears on the display until the function has been
successfully performed on the following day or, for example, until
operation is ended by adjusting the operating mode switch.
The controller's water heating and warm-up optimisation functions
are blocked during adaptation.
Heating circuit 2 (continued)
13