Remko wireless remote control, For multitalent heat pump manager – REMKO MHP-Manager Wireless Remote Control User Manual
Page 12

Heating circuit 2
Parameter
Value range
Default OV Comments
Target room temp. 1 *)
5°C - 40°C
20°C
Adjust the desired room temperature
Target room temp. 1 => operates during the first enable time,
Target room temp. 2 => operates during the second enable time,
Target room temp. 3 => operates during the third enable time
of the heating programme active for this heating circuit.
Target room temp. 2 *)
5°C - 40°C
20°C
Target room temp. 3 *)
5°C - 40°C
20°C
Reduction temp. *)
5°C - 40°C
15°C
Desired room temperature for nighttime heat reduction
Away temp.
5°C - 40°C
15°C
Desired room temperature during the holidays
BoB value
0K - 20K
0K
At a value >0, no burner is permitted to start up, provided that
the room temperature is still above the set target room tem-
perature (BoB value).
This function can be influenced by external,
alternative energy-producing appliances, which have a bus
connection (e.g. SD3 CAN)!
Day heating threshold
----, (-5)°C - 40°C 19°C
Only applicable if the function is activated => setting
“Specialist/Heating circuit/Pump function = Heating thresholds
=> Pump switching according to heating threshold”
If the outdoor temperature measured and determined by the
controller exceeds the heating threshold set here, the heating
will lock, the pumps shut off and the mixers close. The heating
will be enabled again if the outdoor temperature falls below
the set heating threshold by 1K (= 1°C).
Day heating threshold => operates during heating periods
Day heating threshold => operates during reduction periods
“----” => Heating threshold is deactivated. The circulation
pump is switched in accordance with the default function (see
chapter “Circulation pump switching”)
Night heating threshold ----, (-5)°C - 40°C 10°C
*) or depending on the function selected in the Specialist => “HC function” sub-menu
for the heating circuit, also
Const. day supply temp. (constant supply temperature, heating periods)
Const. night supply temp. (constant supply temperature, reduction periods)
At commissioning, check
the heating circuit curve
setting:
Setting 1.20 to 0.6
NOTE
REMKO WIRELESS REMOTE CONTROL
FOR MULTITALENT HEAT PUMP MANAGER
12