Remko wireless remote control, For multitalent heat pump manager – REMKO MHP-Manager Wireless Remote Control User Manual

Page 14

background image

Parameter

Value range

Default

OV

Comments

Room influence

00 - 20

10

The room sensor influence is only active when the analogue
room device FBR (room sensor + mode selection) is
connected.
The HA temperature is increased by the set value if the
desired room temperature is fallen below by 1K.
=> High values will result in rapid regulation with large
variations in HA temperature.
- - - - => Purely weather-based regulation
0 => Purely weather-based regulation *)
20

=> Purely room-temperature-based regulation

Room sensor adj.

(-5.0)K - (5.0)K

0.0K

In the case of room-temperature-based regulation, the
measurement can be corrected (adjusted) using this setting
value, if a measuring error occurs in the connected room sensor.

Warm up opt.

Off, Outdoor
temp.,
Room temp.

Off

Warm-up optimisation activates the function to automatically
bring forward the start of the heating period.
Example: Heating programme 6:00am – 10:30pm
OFF: at 6:00am the heating in the property is switched on.
ON: based on the weather and the current room
temperature, the heating is switched on early enough
to ensure that the property reaches the set target room
temperature at 6:00am.

00 => no bringing forward the start of heating
01 => brought forward based on the weather
02 => brought forward based on the room temperature
Warm-up optimisation only takes place if the
reduction period of the heating circuit is at least 6 hours.

Max. warm-up time

0:00 - 3:00 [h]

2:00 [h]

Bringing the start of heating forward by the maximum
amount is only active if “Warm-up optim. = Outdoor temp.
or Room temp”.
The start of heating is brought forward by no more than this
amount.

Reduction opt.

0:00 - 3:00 [h]

0:00 [h]

Automatic optimisation of the locking of the burner at
the end of the set heating period.
During the set heating period before the heating ends
(for the last heating period only), the burner is no longer
started if it is not already in operation.
Function prevents the heating appliance from heating up
for a short period at the end of the heating period.

PC enable

0000 - 9999

0000

Code no. to allow access to the heating circuit data via PC
“0000” => access is blocked.

Heating circuit 2 (continued)

*) Special function for room influence = 0

If there is a one-off demand for heating during the night reduction period, the heating circuit pump continues to run until the next heating period
(see chapter Circulation pump switching).

REMKO WIRELESS REMOTE CONTROL

FOR MULTITALENT HEAT PUMP MANAGER

14