Parameter
Value range
Default
OV
Comments
HC function
Default,
Const. supply
temp.
Default
Heating circuit function selection
Default => default heating circuit
Const. supply temp. => regulation based on fixed supply
temperatures
During the heating periods (see heating programme),
the heating circuit is operated with set fixed supply
temperature [Day supply temp.]; during reduction periods
on the other hand, it is operated accordingly with set fixed
supply temperature [Night supply temp.]. These parameters
appear after selecting [Const. supply temp.] in the User
menu under Heating circuit.
HCP operation
Default,
Heating limits,
Time prog. only,
Continuous
operation
Default
Pump operating mode
The circulation pumps are shut off if there is no heating
requirement. Mixers are closed at the same time => “The
heating circuit is shut off”.
(Switch on with 1K hysteresis)
Default => default circulation pump switching
- Room-based regulation
OFF: Room temperature > Set room target value + 1K
- Weather-based regulation during heating mode
OFF: Outdoor temperature > Set room target value
- Weather-based regulation during reduction mode
(Room influence =0)
OFF: The switching off takes place during the transition
to reduction mode. After switching on, the pump runs
continuously.
ON: Room temperature < Room target value
(Room influence =“--”)
OFF: Target supply temperature < 20°C.
Heating limits => pump switching based on heating limits
- Heating period
OFF: Outdoor temperature < Set day heating limit
- Reduction period
OFF: Outdoor temperature < Set night heating limit
Time prog only => pump switching based on heating
programme
Heating period: pump is ON; heating circuit is free
Reduction period: pump is OFF; heating circuit is locked
Continuous operation
The pump runs 24hrs a day! The heating circuit is
continuously free.
Heating circuit 1/2
REMKO WIRELESS REMOTE CONTROL
FOR MULTITALENT HEAT PUMP MANAGER
22