Parameter

Value range

Default

OV

Comments

Max supply temp.

20°C - 110°C

55°C

The calculated target supply temperature for the heating
circuit is limited by the set maximum supply temperature
(overheating protection).

The heating circuit pump for the direct heating circuit is
only switched off if the HA temperature exceeds the set
maximum supply temperature by 8K. The heating circuit
pump is switched back on again if the
HA temperature falls below the temperature [maximum
supply temperature + 5K]!

Min supply temp.

10°C - 110°C

18°C

The calculated target supply temperature for the heating
circuit is increased to the set minimum supply temperature
(e.g. for air heating).

Frost protection
temp.

----;(-15)°C – (5)°C

5°C

If the outdoor temperature falls below the programmed
value, the system switches into frost protection mode
(pumps switch on).
“----” Frost protection function is deactivated!

Outdoor temp. delay 0:00 - 24:00

1:00

The outdoor temperature delay selected must take the
building design into account. Because a change in outdoor
temperature subsequently impacts the room temperature,
for a building of heavy construction (thick walls), a long
delay must be selected. For a building of lightweight
construction (in which the walls do not store heat), the
delay should be set to (0 hrs).

Curve distance

0K - 50K

0.0K

Heating curve distance
The required HA temperature for a mixer circuit is
calculated by adding the calculated target temperature for
the heating circuit supply to the heating curve distance.
The heating curve distance equalises sensor tolerances and
heat losses as far as the mixer.

Demand requirement Off/On

On

Enable the circuit
On => The heating circuit can be used with higher-level
functions (e.g. cooling function of a heating appliance to
protect against overheating; heat dissipation in service
mode) as a heat sink/consumer. The heating circuit is
heated to the set maximum supply temperature for the
duration of the function.

I-controller

Off, 3:00am -
0:15am

Off

Integrated controller part (e.g. 30 min)
If there is a difference in room temperature of 1K for the
set period, the supply temperature is increased by the
value “Room sensor influence”.
Usual value: “30 min”.

Heating circuit (continued)